Select the Cal Type menu option and then the Loop Test menu option from the Cal Type Selection Screen.
This will access the Loop Cal Type Selection Screen shown at right below. Use this screen to select the
desired loop test procedure.
















Move the cursor to the desired Loop Cal Type procedure and press the Save soft key. The MFT display returns
to the Calibrate Key Main Menu Screen. Select Begin Calibration option to start the Begin Calibration Setup
Screen shown below.

















Enter the Tag number and Loop ID by moving cursor down to the corresponding menu option and pressing
Select. Use the alphanumeric entry system of the MFT to enter the proper tag and press the Done soft key.
Answer Yes to save the loop tag, confirm the information on Begin Calibration Setup Screen is correct, and
then Select the Begin Calibration menu line when satisfied.

If 1 pt, 2 pt, 3 pt or 5 pt Loop Test was selected then the Loop Test will launch as follows.












Cal
Cal Type: Loop, 2pt
4-20 mA, 2 pt
4-12-20 mA, 3 pt
4-8-12-16-20 mA, 5 pt
4 mA, 1 pt
20 mA, 1 pt
Custom





Up Down Save Back

Loop Cal Type Selection Screen

Cal
Cal Type: P
P

TC
RTD

VMA
I/P
P/I
Switch

Loop Test



Up Down Save Back

Cal Type Selection Screen

Cal

Hart Calibration
Begin Calibration

Tag: PT-11008

SN: 2878023

Meas/Sim: S1
LRV: 4.000

URV: 20.000
Loop ID: Default
< More>

Up Down Select Back

Begin Calibration Setup Screen