SP4000 Flow Computer

6.11
CURRENT
OUTPUT

CURRENT OUTPUT

2

RATE

1

TOTAL

Select the current output to be configured. The flow computer offers
two current outputs.

Selection:

1 (Current output 1)
2 (Current output 2)

Display:

1
SELECT OUTPUT

Assign a variable to the current output.

Selection:

HEAT FLOW, MASS FLOW,
COR. VOLUME FLOW, VOLUME FLOW,
TEMPERATURE, TEMPERATURE 2,
DELTA TEMPERATURE, PRESSURE, DENSITY, PEAK
DEMAND, DEMAND LAST HOUR

Display:

VOLUME FLOW
ASSIGN CURRENT OUT.

Define the 0 or 4 mA low scale current value. The current for the
scaled full scale value is always 20 mA.

Selection:

0-20 mA, 4-20 mA, NOT USED

Display:

4-20 mA
CURRENT RANGE

Set the low scale value to the 0 or 4 mA current signal for the
variable assigned to the current output.

Input:

Number with floating decimal point: -999999...+999999

Display:

.000 ft3/h
LOW SCALE VALUE

Set the full scale value to the 20 mA current signal for the variable
assigned to the current output.

Input:

Number with floating decimal point:
-999999...+999999

Display:

1000.00 ft3/h
FULL SCALE VALUE

SELECT OUTPUT

ASSIGN CURRENT
OUT

CURRENT RANGE

LOW SCALE

FULL SCALE

2

RATE

1

TOTAL