beautypg.com

Pulse output – Liquid Controls SP4000 User Manual

Page 77

background image

74

SP4000 Flow Computer

6.10
PULSE
OUTPUT
(Continued)

PULSE OUTPUT

Define the flow quantity per output pulse. This is expressed in units
per pulse (i.e. ft

3

/ pulse).

Note:

Ensure that the max. flowrate (full scale value) and the pulse
value entered here agree with one another. The max.
possible output frequency is 50Hz. The appropriate pulse
value can be determined as follows:

Pulse value >

estimated max. flowrate (full scale)/sec

required max. output frequency

Input:

Number with floating decimal point: 0.001...10000.0

Display:

1.000 ft3/P
PULSE VALUE

Set the pulse width required for external devices. The pulse width
limits the max. possible output frequency of the pulse output. For a
certain output frequency, the max permissible pulse width can be
calculated as follows:

Pulse width <

1 .

2 • max. output frequency (Hz)

Input:

Number with floating decimal point:
0.01...9.999 s (seconds)

Display:

.01 s
PULSE WIDTH

Frequency signals can be simulated in order to check any instrument
that is connected to the pulse output. The simulated signals are
always symmetrical (50/50 duty cycle).

Note:

• The simulation mode selected affects the frequency output.

The flow computer is fully operational during simulation.

• Simulation mode is ended immediately after exiting this

submenu.

Selection:

OFF, 0.0 Hz, 0.1 Hz, 1.0 Hz, 10 Hz, 50 Hz

Display:

OFF
SIMULATION FREQ>

PULSE VALUE

PULSE WIDTH

SIMULATION FREQ.

2

RATE

1

TOTAL

2

RATE

1

TOTAL