SP4000 Flow Computer

OTHER INPUT

6.9
OTHER
INPUT
(Continued)

Enter the actual atmospheric pressure. When using gauge pressure
transmitters for determining gas pressure, the reduced atmospheric
pressure above sea level is then taken into account.

Input:

Number with floating decimal point:
0.0000...10000.0

Display:

1.013 bara
BAROMETRIC PRESS.

Enter the temperature at which the flowmeter was calibrated. This
information is used in the correction of temperature induced effects
on the flowmeter body dimensions.

Input:

Number with fixed decimal point:
-9999.99...+9999.99

Display:

68.00 of
CALIBRATION TEMP.

BAROMETRIC PRESS.

CALIBRATION TEMP.

2

RATE

1

TOTAL

2

RATE

1

TOTAL

This feature is used to see the present value of the compensation
input signal. The type of electrical signal is determined by the
compensation input signal type selection.

Display:

20 mA
VIEW INPUT SIGNAL

VIEW INPUT SIGNAL

Enter the TRAP ERROR DELAY

(cold trap error)

in HH:MM format.

An

alarm will only be activated if the trap is detected as continuously being in the
abnormal states for a time period greater than this TRAP ERROR DELAY
time.

Display:

HH:MM
TRAP ERROR DELAY

TRAP ERROR DELAY

Enter the TRAP BLOWING DELAY

(trap stuck open)

in HH:MM format.

An alarm will only be activated if the trap is detected as continuously being in
the abnormal states for a time period greater than this TRAP BLOWING
DELAY time.

Display:

HH:MM
TRAP BLOWING DELAY

TRAP BLOWING
DELAY