5.2 General Operation

This instrument is used primarily to monitor flowrate and accumulated total. The inputs
can be software configured for a variety of flowmeter, temperature and pressure sensors.
The standard output types include: Pulse, Relay, Analog and RS-232 The unit can
display the flowrate, total and process variables. RS-485 is an available option for a
second communication channel.

5.3 Password Protection

After an Private and/or Service Code is entered in the "System Parameters" Submenu
Group. (see section 6.3, Private Code and Service Code sub-menus), the unit will be
locked. The unit will prompt the user for the password when trying to perform the
following functions:

Clear Totals
Clear Grand Totals (service code required)
Edit a Setup Menu Item
Edit Alarm Setpoints (ALARM 1 & ALARM 2 Keys)

The Service Code should be reserved for service technicians. The Service Code will
allow access to restricted areas of the Service and Test menus. Changes in these
areas may result in lost calibration information.

5.4 Relay Operation

Two relay alarm outputs are standard. The relays may also be used for pulse outputs.
The relays can be assigned to trip according to various rate, total, temperature or
pressure readings. The relays can be programmed for low/high alarms, latch or unlatch,
or as relay pulse outputs.
ALARM SETPOINT 1 (RLY1) and ALARM SETPOINT 2 (RLY2) are easily accessible
by pressing the ALARM 1 or ALARM 2 key on the front panel.

5.5 Pulse Output

The isolated pulse output is menu assignable to any of the available totals. The pulse
output duration and scaling can be set by the user. The pulse output is ideal for
connecting to remote totalizers or other devices such as a PLC. See section 1.2 for
electrical specifications.

5.6 Analog Outputs

The analog outputs are menu assignable to correspond to any of the process parameters.
The outputs are menu selectable for 0-20 mA or 4-20 mA. The analog outputs are ideal
for "trend" tracking using strip chart recorders or other devices.

5.7 Function Keys; Display Grouping

TOTAL

Press the

to view HEAT TOTAL, MASS TOTAL, CORRECTED VOLUME

TOTAL, VOLUME TOTAL

GRAND TOTAL

Press the

to view GRAND HEAT, GRAND MASS, GRAND CORRECTED

VOLUME, GRAND VOLUME

RATE

Press the

to view HEAT, MASS , CORRECTED VOLUME, VOLUME,

PEAK DEMAND, DEMAND LAST HOUR

TEMPERATURE

Press the

to view TEMPERATURE 1, TEMPERATURE 2, DELTA

TEMPERATURE, DENSITY

PRESSURE

Press the

to view PRESSURE, DIFFERENTIAL PRESSURE, , Y

1

,

SPECIFIC ENTHALPY

TIME

Press the

to view TIME/DATE, PEAK TIME/DATE, ACCUMULATIVE

POWER LOSS TIME, TIME OF LAST POWER OUTAGE, TIME POWER

WAS LAST RESTORED

General
Operation

Password Protection

Relay Operation

Pulse Output

Analog Outputs

Function Keys
Display Grouping