SP4000 Flow Computer

FLUID DATA

2

RATE

1

TOTAL

6.7
FLUID DATA
(Continued)

2

RATE

1

TOTAL

2

RATE

1

TOTAL

Enter the thermal expansion coefficient for a generic liquid. The
coefficient is required for the temperature compensation of volume
with various flow equations (i.e. Liquid Mass or Corrected Liquid
Volume).

Input:

Number with floating decimal point: 0.000...100000 (e-6)

The thermal expansion coefficient can be calculated as follows:

c =

1 -

ρ

(T

1

)

ρ

(T

0

)

T

1

- T

0

• 10

6

c

Thermal expansion coefficient

T

0

,T

1

Temperatures at known points (see below)

ρ

(T

0

,T

1

)

Density of the liquid at temperature T

0

or T

1

For optimum accuracy, choose the reference temperatures
as follows:
T

0

: midrange temperature

T

1

: choose a second point at or near the maximum process

temperature

10

6

The value entered is internally multiplied by a factor of 10

-6

(display: e-6/temp. unit) since the value to be entered is
very small.

Display:

104.300 (e-6/oF)
THERM.EXP.COEF.

Enter the specific combustion heat for generic fuels.

Input:

Number with floating decimal point: 0.000...100000

Display:

1000.000 kBtu/lbs
COMBUSTION HEAT

Enter the specific heat capacity for generic fluids. This value is
required for calculating the delta heat of liquids.

Input:

Number with floating decimal point: 0.000...10.000

Display:

10.000 kBtu/lbs-

°

F

SPECIFIC HEAT

THERM. EXP. COEF.

COMBUSTION HEAT

SPECIFIC HEAT