SP4000 Flow Computer

FLUID DATA

6.7
FLUID DATA

Select the fluid. There are three types:

1. Steam / Water
All information required for steam and water (such as saturated steam
curve, density and thermal capacity) is permanently stored in the flow
computer.

2. Fluid Displayed
Preset information for other fluids (such as air and natural gas) is
stored in the flow computer and can directly adopted by the user.

If the preset values need to be changed to fit your specific process
conditions, then proceed as follows:
Select the fluid (air or natural gas) and press the ENTER key (this
sets all of the preset values).
Re-select the submenu group "FLUID TYPE", now choose
"GENERIC" and ENTER. Now the preset values for the previously
selected fluid can be altered.

3. Generic Fluid
Select the setting "GENERIC" for the Fluid type submenu. The
characteristics of any fluid can now be defined by the user.

Selection:

GENERIC, WATER, SATURATED STEAM, SUPERHEATED
STEAM, DRY AIR, HUMID AIR, HUMID GAS, NATURAL
GAS, NATURAL GAS (NX-19), HYDROGEN, ARGON,
METHANE, NITROGEN, CARBON DIOXIDE, PROPANE,
OXYGEN, ETHANE, HELIUM

Display:

GENERIC
FLUID TYPE

Select the density for a generic fluid at reference temperature and
pressure (see "STP REFERENCE" in "OTHER INPUT" submenu
group).

Input:

Number with floating decimal point: 0.0001...10000.0

Display:

.0760 #/ft3
REF. DENSITY

FLUID TYPE

REF. DENSITY