Screen 19c: Preset and Delivery (3/7)

Preset and Delivery

The third Preset and Delivery screen is used to set a few

delivery options.

Product # and Units will reflect values

selected in the previous screens.
Product Type is the current product type associated

with the selected

Product # as defined in the Calibration

screens.
Aux1 and Aux2 are used to define the function of auxiliary

outputs 1 and 2. If there are no external devices attached

to these two outputs, there is no need set these values.

Move the pointer to

Aux1 and press ENTER to open a

list box window with the following options:
Monitor Flow Rate: This option causes auxiliary 1 to

activate at the beginning of each delivery. If the flow

rate during the delivery meets or exceeds 40 units

per minute, auxiliary 1 will deactivate. This option is

typically used to monitor the amount of restriction in

a strainer basket or filter. The idea being, when the

filter or strainer is getting clogged, the flow rate will

decrease.

Off: This option deactivates auxiliary 1.
On: This option activates auxiliary 1. It remains activated

even when a delivery is not taking place.

On During Delivery: This option activates auxiliary output

only when the system is in an active delivery. This

also causes header line 11 to print on the ticket.

Move the pointer to

Aux2 and press ENTER to open a

list box windows with the following options:
Flow Direction: This option causes auxiliary 2 to indicate

the flow direction through the flow meter.

Off, On, On During Delivery are all defined as in Aux1

above. If set to

On During Delivery, header line 12

will print on the ticket.

No-Flow Timer is used to set the no flow timer for the

next delivery. Move the pointer to

No-Flow Timer and

press

ENTER to open a field edit window. Enter a value

between “

0” and 3600 seconds. This timer will end an

active delivery if there is no flow through the meter in

the set amount of time. If this value is set to “

0”, then

each delivery ticket will contain the text

“MULTIPLE

DELIVERIES AT ONE SITE. This value is typically set

to

180 (3 minutes).

Press

Next (F1) to advance to Screen 19d on page 57.

(3/7) 1

Units: Gallons

Gasoline

On During Delivery

Flow Direction

180

PRESET AND DELIVERY

Product#: 1

Product Type:

Aux1:

Aux2:

No-Flow Timer: