Burkert Type 8136 User Manual
Page 50

Maintenance: Due to external influences, the instrument function is
limited. The measurement is affected, but the measured value is still
valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
The following table shows the error codes in the status message
"F
ailure" and gives information on the reason and rectification. Keep in
mind that some information is only valid with four-wire instruments.
Code
Text mes-
sage
Cause
Rectification
F013
no measured
value avail-
able
l Sensor does not detect an
echo during operation
l Antenna system contami-
nated or defective
l Check or correct installa-
tion and/or parameter ad-
justment
l Clean or exchange process
component or antenna
F017
Adjustment
span too small
l Adjustment not within
specification
l Change adjustment ac-
cording to the limit values
(difference between min.
and max. ≥ 10 mm)
F025
Error in the
linearization
table
l Index markers are not
continuously rising, for ex-
amle unlogical value pairs
l Check linearization table
l Delete table/Create new
F036
No operable
software
l Failed or interrupted soft-
ware update
l Repeat software update
l Check electronics version
l Exchange of the elec-
tronics
l Send instrument for repair
F040
Error in the
electronics
l Hardware defect
l Exchange of the elec-
tronics
l Send instrument for repair
F080
l General software error
l Separate operating voltage
briefly
F105
Determine
measured val-
ue
l The instrument is still in the
start phase, the measured
value could not yet be
determined
l Wait for the warm-up phase
l Duration depending on the
version and parameter ad-
justment up to approxi-
mately 3 min.
F113
Communica-
tion error
l EMC interferences
l Transmission error with the
external communication
with 4-wire power supply
unit
l Remove EMC influences
l Exchange 4-wire power
supply unit or electronics
Failure
50
LEVEL TRANSMITTER 8136 • 4 … 20 mA/HART - two-wire
9 Diagnosis, Asset Management and service
41783
-EN
-120316