96

Operatingandfunctions

REtURN

OUtPUt

DO1

END DOSE

DO2

iNV YES

iNV NO

0......9

Choose the operating, inverted or not inverted, of the
output.

Confirm.

DO3

DO4

DO4

Figure 79:

Configuring the output DO1 or DO3 or DO4 to signal the end of the dosing

If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press

ENTER

to save the settings or not and go back to the Process level.

9.7.22 Configuring the transistor output Do1 or Do4 as a pulse

output proportional to a volume or a mass

When the DO1 or DO4 transistor output is configured as a pulse output proportional to a volume or a mass, a
pulse is transmitted on the output each time the parametered volume or mass of fluid has been measured by the
device.

• When the frequency emitted on the pulse output is between 0,6 and 300 Hz, the duty cycle of the

signal is between 45% and 60%.

• When the frequency emitted on the pulse output is between 300 and 1500 Hz, the duty cycle of the

signal is between 40% and 50%.

• When the frequency emitted on the pulse output is between 1500 and 2200 Hz, detection on a pulse

edge is possible.