To a volume or a mass – Burkert Type 8035 User Manual
Page 98
96
Operatingandfunctions
REtURN
OUtPUt
DO1
END DOSE
DO2
iNV YES
iNV NO
0......9
→
Choose the operating, inverted or not inverted, of the
output.
→
Confirm.
DO3
DO4
DO4
Figure 79:
Configuring the output DO1 or DO3 or DO4 to signal the end of the dosing
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.
9.7.22 Configuring the transistor output Do1 or Do4 as a pulse
output proportional to a volume or a mass
When the DO1 or DO4 transistor output is configured as a pulse output proportional to a volume or a mass, a
pulse is transmitted on the output each time the parametered volume or mass of fluid has been measured by the
device.
• When the frequency emitted on the pulse output is between 0,6 and 300 Hz, the duty cycle of the
signal is between 45% and 60%.
• When the frequency emitted on the pulse output is between 300 and 1500 Hz, the duty cycle of the
signal is between 40% and 50%.
• When the frequency emitted on the pulse output is between 1500 and 2200 Hz, detection on a pulse
edge is possible.
English
Type 8025 - 8035 BATCH