beautypg.com

Is green, Mation menu – Burkert Type 8035 User Manual

Page 121

background image

119

Maintenanceandtroubleshooting

10.3.5 resolution of problems without message generation and

the device status leD is green

Device state
leD

possible cause

recommended action

green

During a dosing, the displayed quantity is
increased or decreased very slowly.

Check that the K factor corresponds to the
fitting used.

Do a teach-in procedure to determine the K
factor of the fitting used.

Check that the flow rate in the pipe is high
enough.

green

The dosing does not start although the pro-
cedure has been correctly started:

• Either the dosing quantity times the set K

factor is lower than 6.

Set a dosing quantity that is higher or equal to
6 divided by the set K factor.

• Either the pipe diameter is too high for the

dosing of small quantities.

Reduce the pipe diameter.

green

The display shows that the dosing has started
(the units blink) but the valve connected to
DO2 and/or DO3 does not open.

Check the value of the time delay before
opening of the valves.

Check that the flow rate in the pipe is high
enough.

10.3.6 resolution of problems linked to warning messages not

registered in the information menu

Device state
leD

output Do4 in
"stAte" mode

message
displayed

possible cause

recommended action

any colour

-

"PU L LIM"

The message is displayed after
the pulse value has been entered
(parameter "PU" of the transistor
output DO1) or upon validation
of the settings of the Parameters
menu.

The pulse value times the K factor
of the device is > 1000000.

The quantity entered for a pulse is
too high.

Enter a lower quantity
per pulse. See chap.
“9.7.22”.

English

Type 8025 - 8035 BATCH

This manual is related to the following products: