Is green, Mation menu – Burkert Type 8035 User Manual
Page 121
119
Maintenanceandtroubleshooting
10.3.5 resolution of problems without message generation and
the device status leD is green
Device state
leD
possible cause
recommended action
green
During a dosing, the displayed quantity is
increased or decreased very slowly.
→
Check that the K factor corresponds to the
fitting used.
→
Do a teach-in procedure to determine the K
factor of the fitting used.
→
Check that the flow rate in the pipe is high
enough.
green
The dosing does not start although the pro-
cedure has been correctly started:
• Either the dosing quantity times the set K
factor is lower than 6.
→
Set a dosing quantity that is higher or equal to
6 divided by the set K factor.
• Either the pipe diameter is too high for the
dosing of small quantities.
→
Reduce the pipe diameter.
green
The display shows that the dosing has started
(the units blink) but the valve connected to
DO2 and/or DO3 does not open.
→
Check the value of the time delay before
opening of the valves.
→
Check that the flow rate in the pipe is high
enough.
10.3.6 resolution of problems linked to warning messages not
registered in the information menu
Device state
leD
output Do4 in
"stAte" mode
message
displayed
possible cause
recommended action
any colour
-
"PU L LIM"
The message is displayed after
the pulse value has been entered
(parameter "PU" of the transistor
output DO1) or upon validation
of the settings of the Parameters
menu.
The pulse value times the K factor
of the device is > 1000000.
The quantity entered for a pulse is
too high.
→
Enter a lower quantity
per pulse. See chap.
“9.7.22”.
English
Type 8025 - 8035 BATCH