28
Installationandwiring
1
2
3
→
Respect the installation instructions given in the operating instructions
of the fitting.
→
Insert the electronic module SE35 [2] in the sensor-fitting S030 [1].
→
Secure the electronic module to the sensor-fitting by a 30° turn.
→
Secure the unit by tightening screw [3].
Figure 15:
Installation of a 8035 Batch
7.6
Wiring
danger
risk of injury due to electrical voltage.
▶ Shut down the electrical power source of all the conductors and isolate it before carrying out work on the
system.
▶ Observe all applicable accident protection and safety regulations for electrical equipment.
Insert the supplied stopper gaskets into the unused cable glands of a compact or wall-mounted version to
ensure the tightness of the device.
Only move the selectors when the power supply is off.
• Use a filtered and regulated 12-36 V DC power supply.
• Make sure the installation is equipotential. See chap. “7.6.1”.
• Use shielded cables with a temperature limit of 80 °C minimum.
• Do not install the cables near high voltage or high frequency cables; If this cannot be avoided, observe a
min. distance of 30 cm.
• Protect the device power supply by means of a 300 mA fuse and a switch.
• Protect the power supply of each transistor output by means of a 125 mA fuse.
• Protect the relays by means of a max. 3 A fuse and a circuit breaker (depending on the process).
• Do not apply both a dangerous voltage and a safety extra-low voltage to the relays.
English