beautypg.com

6 wiring, Wiring – Burkert Type 8035 User Manual

Page 30

background image

28

Installationandwiring

1

2

3

Respect the installation instructions given in the operating instructions
of the fitting.

Insert the electronic module SE35 [2] in the sensor-fitting S030 [1].

Secure the electronic module to the sensor-fitting by a 30° turn.

Secure the unit by tightening screw [3].

Figure 15:

Installation of a 8035 Batch

7.6

Wiring

danger

risk of injury due to electrical voltage.

▶ Shut down the electrical power source of all the conductors and isolate it before carrying out work on the

system.

▶ Observe all applicable accident protection and safety regulations for electrical equipment.

Insert the supplied stopper gaskets into the unused cable glands of a compact or wall-mounted version to
ensure the tightness of the device.

Only move the selectors when the power supply is off.

• Use a filtered and regulated 12-36 V DC power supply.

• Make sure the installation is equipotential. See chap. “7.6.1”.

• Use shielded cables with a temperature limit of 80 °C minimum.

• Do not install the cables near high voltage or high frequency cables; If this cannot be avoided, observe a

min. distance of 30 cm.

• Protect the device power supply by means of a 300 mA fuse and a switch.

• Protect the power supply of each transistor output by means of a 125 mA fuse.

• Protect the relays by means of a max. 3 A fuse and a circuit breaker (depending on the process).

• Do not apply both a dangerous voltage and a safety extra-low voltage to the relays.

English

Type 8025 - 8035 BATCH

This manual is related to the following products: