beautypg.com

Burkert Type 8035 User Manual

Page 20

background image

18

Technicaldata

Power supply 115/230 V AC

• frequency

• supplied voltage

• current, 8025 wall-mounted version

• current, 8025 and 8035 compact versions

• integrated protection, compact version

• integrated protection, wall-mounted version

• power, 8025 wall-mounted version

• power, 8025 and 8035 compact versions

• 50/60 Hz

• 27 V DC, regulated

• max. 250 mA

• max. 125 mA

• 125 mA time delay fuse

• 250 mA time delay fuse

• 6 VA

• 3 VA

Current consumption (without the consumption
of the loads, the inputs and the transistor
outputs)

• 12-36 V DC fed version

• 115/230 V AC fed version


• 90 mA (at 12 V DC) and 45 mA (at 36 V DC), with the

consumption of the relay outputs

• 55 mA, with the consumption of the relay outputs

Transistor outputs DO1 and DO4

• type

• DO1 function

• DO4 function

• frequency (f)

• Electrical data

• duty cycle if 0,6 < f < 300 Hz, all versions

• duty cycle if 300 < f < 1500 Hz, 8025 wall-

mounted and panel-mounted versions

• duty cycle if 1500 < f < 2200 Hz, 8025 wall-

mounted and panel-mounted versions

• protection

• NPN/PNP (through wiring), polarized, potential-free

• pulse output (can be configured and parametered)

• dosing state (can be configured and parametered)

• 0,6-2200 Hz

• 5-36 V DC, 100 mA max., voltage drop 2,7 V DC at

100 mA

• > 0.45

• > 0.4

• < 0.4

• galvanically isolated, and protected against overvoltages,

polarity reversals and short-circuits

relay outputs (Do2 and Do3)

• type

• DO2 function

• DO3 function

• electrical data of the load (non UL devices)

• electrical data of the load (UL devices)

• max. breaking capacity

• normally open, can be inverted through parameter setting

• valve 100%, cannot be modified

• alarm (can be configured and parametered)

• 230 V AC / 3 A or 40 V DC / 3 A

• max. 30 V AC and 42 V peak or max. 60 V DC, 3 A

• 750 VA (resistive load)

English

Type 8025 - 8035 BATCH

This manual is related to the following products: