18
Technicaldata
Power supply 115/230 V AC
• frequency
• supplied voltage
• current, 8025 wall-mounted version
• current, 8025 and 8035 compact versions
• integrated protection, compact version
• integrated protection, wall-mounted version
• power, 8025 wall-mounted version
• power, 8025 and 8035 compact versions
• 50/60 Hz
• 27 V DC, regulated
• max. 250 mA
• max. 125 mA
• 125 mA time delay fuse
• 250 mA time delay fuse
• 6 VA
• 3 VA
Current consumption (without the consumption
of the loads, the inputs and the transistor
outputs)
• 12-36 V DC fed version
• 115/230 V AC fed version
• 90 mA (at 12 V DC) and 45 mA (at 36 V DC), with the
consumption of the relay outputs
• 55 mA, with the consumption of the relay outputs
Transistor outputs DO1 and DO4
• type
• DO1 function
• DO4 function
• frequency (f)
• Electrical data
• duty cycle if 0,6 < f < 300 Hz, all versions
• duty cycle if 300 < f < 1500 Hz, 8025 wall-
mounted and panel-mounted versions
• duty cycle if 1500 < f < 2200 Hz, 8025 wall-
mounted and panel-mounted versions
• protection
• NPN/PNP (through wiring), polarized, potential-free
• pulse output (can be configured and parametered)
• dosing state (can be configured and parametered)
• 0,6-2200 Hz
• 5-36 V DC, 100 mA max., voltage drop 2,7 V DC at
100 mA
• > 0.45
• > 0.4
• < 0.4
• galvanically isolated, and protected against overvoltages,
polarity reversals and short-circuits
relay outputs (Do2 and Do3)
• type
• DO2 function
• DO3 function
• electrical data of the load (non UL devices)
• electrical data of the load (UL devices)
• max. breaking capacity
• normally open, can be inverted through parameter setting
• valve 100%, cannot be modified
• alarm (can be configured and parametered)
• 230 V AC / 3 A or 40 V DC / 3 A
• max. 30 V AC and 42 V peak or max. 60 V DC, 3 A
• 750 VA (resistive load)
English