Operatingandfunctions

9.6.7

Doing a dosing in dosing mode "loC. rep."

The dosing mode "LOC. REP." allows for starting, via the navigation keys, the dosing of the quantity determined
by a Teach-In procedure.

danger

Danger due to electrical voltage.

▶ Shut down the electrical power source of all the conductors and isolate it before carrying out work on the

system.

▶ Observe all applicable accident protection and safety regulations for electrical equipment.

Wire the output DO4 as described in “Figure 36”.

Connect the valves to the DO2 and DO3 outputs: see chap. 7.6.12.

Start the device again.

Configure the device with this dosing mode: see chap. 9.7.13.

Do a dosing as shown in “Figure 52”.

• If the generation of alarms (alarm "DURING") for problems occuring during a dosing has been activated

(see chap. “9.7.16”), an alarm is generated if there is no flow rate measured in the pipe whereas the
valves are open. See chap. “10.3.4” to solve the problem.

• If the generation of alarms (alarm "AFTER") for problems occuring at the end of the dosing has been

activated (see chap. “9.7.17”), an alarm is generated if there is still flow in the pipe whereas the valves
are closed. See chap. “10.3.4” to solve the problem.