Installationandwiring
7.4
installation of a wall-mounted version
note
risk of material damage if the cable glands are not tightly screwed on the housing
▶ Before installing the wall-mounted housing on its support, tighten the nuts of the entry item of the cables
glands at a torque of 1.5 Nm.
The device in a wall-mounted version has 4 holes in the bottom of the housing.
→
Remove the blanking strips covering the screws.
Blanking strips
ENTER
0....9
FLOW
Nut of the entry item
→
Loosen the 4 screws and open the cover to get access to the holes [1].
1
1
1
1
106 mm
230V
L N
230V
T 250 mA
5 6 7 8 9 10
L N
230V
CURRENT
SOURCE
SINK
BINARY
PE
PE
PE
PE
DI1
DI2
DI3
DI4
DO4
ISOG
FLOW
SENSOR
L+
L-
PE P- P+
NC
Iout
PULSE
DO1
Supply
12..36Vdc
Univ
Batch
(AO1)
SUPPLY
NC
COIL
PULSE INPUT
NPN/PNP
2
1
3
PE
+
-
SENSOR
SUPP
LY
LOAD
+5V
L+
(L+)-12V
COIL/PNP
39K
470
2.2K
SENSOR TYPE
COIL
NPN/PNP
DO2
DO3
OF
FO
N
106 mm
Figure 13:
Installation of a wall-mounted version
→
Secure the housing to the support respecting the dimensions indicated in “Figure 13”.
→
Wire acc. to instructions in chap. “7.6”.
→
Close the housing and tighten the 4 screws of the cover.
7.5
installation of a 8035 Batch
The electronic module SE35 Batch can be installed on a pipe by using a sensor-fitting S030.
→
Observe the fluid temperature/pressure dependency depending on the material of the sensor-fitting S030 used: