Operatingandfunctions
K-FACtOR
K=2.85
tEACH V.
REtURN
0......9
The device calculates the K factor of the fitting
and displays it.
FiLL END
0000.0 L
VALiD N/Y
tEACH F.
OPtiONAL
→
When the tank is full, confirm "FILL END": the valve con-
nected to DO2 is closed.
K=2.90
→
Enter the volume (value between 0.1 and 9999.9 in the units
chosen for the totalizers at the "UNIT" parameter) of fluid
that passed in the circuit.
→
Confirm.
The display shows the K factor of the fitting, last entered or determined
using a Teach-In procedure
→
Confirm the displayed value.
→
Confirm or not the K factor determined through Teach-In.
→
Choose "OK Y" and confirm: the device opens the valve
connected to the relay output DO2 and the fluid flows
through the pipe.
OK Y/N
→
Place a tank with a known volume at the end of the pipe.
Figure 58:
Teach-in procedure depending on a volume
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.
Determining the fitting k factor using a teach-in procedure depending on a flow rate ("teAch f.")
The device uses the new K factor as soon as "SAVE YES" is confirmed when leaving the Parameters
menu.
English
Type 8025 - 8035 BATCH