17
Technicaldata
116
88
88
180
91
21
75
114
105
104
ENTER
0....9
FLOW
Figure 6:
Dimensions of the electronic module SE35 Batch [mm]
Table 2:
Dimension H [mm] of the dosing controller 8035 Batch, depending on the DN of the sensor-fitting S030
Dn
h [mm] with sensor-fitting s030
H
06
134
08
134
15
139
20
137
25
137
32
140
40
144
50
151
65
151
6.3.3
electrical data
Power supply 12-36 V DC
• filtered and regulated
• SELV circuit, with a safe energy level
• max. tolerance 12 V DC: -5 % or +10%
• max. tolerance 36 V DC: ±10 %
Power source (not supplied)
• limited energy source (in accordance to EN 61010-1,
paragraph 9.3)
• or Class 2 source (in accordance to standards
UL 1310/1585 and EN 60950-1)