beautypg.com

Burkert Type 8035 User Manual

Page 120

background image

118

Maintenanceandtroubleshooting

Device
state leD

output Do1
and/or Do2
and/or Do3

output Do4
in "stAte"
mode

message
displayed

possible cause

recommended action

orange,
3,5 Hz
flashing

Switched

2)

3,5 Hz-fre-
quency

"ERROR [T]" The message

can only appear
if the dosing
mode "EXT. [T]" is
active.

The dosing
quantity is
exceeded when
the input DI1 has
been deactivated.

Increase the values of the
parameters A and B in order
to reduce the activation time of
the digital input DI1 and so that
"A*T + B" < flow rate times T.

or set a time delay before
the valves open. See chap.
“9.7.24” and “9.7.25”.

or reduce the flow rate in the
pipe.

Confirm the message by
pressing the key "ENTER" or
by sending out a pulse on DI4:
the current dosing is aborted.

orange,
3,5 Hz
flashing

Switched

2)

3,5 Hz-fre-
quency

"ERROR [T]" The message

can only appear
if the dosing
mode "EXT. [T]" is
active.

The dosing
quantity, deter-
mined by the
device depending
on the activation
duration of the
digital input DI1,
has exceeded
the required
thresholds.

Set the values of the param-
eters A and B and the value
of the activation duration T so
that "A*T+B" < 100 000 and
"A*T+B" times the K factor
of the fitting used is higher or
equal to 6.

Set an activation duration
T < 300 s.

Confirm the message by
pressing the key "ENTER" or
by sending out a pulse on DI4:
the current dosing is aborted.

2)

If the output is configured to switch when an alarm is generated. See chap. “9.7.18”.

English

Type 8025 - 8035 BATCH

This manual is related to the following products: