24 configuring the relay output do2, Configuring the relay output do2 – Burkert Type 8035 User Manual
Page 100
98
Operatingandfunctions
9.7.24 Configuring the relay output Do2
Connect the main valve (installed into the pipe with high flow rate) to the relay output DO2. See chap.
“7.6.12”.
The output DO2 is dedicated to the control of the main valve (installed into the pipe with high flow rate).
→
If the device is connected to a single valve, enter a filling percentage
of 100.
→
If the device is connected to 2 valves and a filling percentage < 100
is entered, the second valve, connected to the relay output DO3, will
fill the remaining quantity.
→
Confirm.
OUtPUt
DO2
100 %
DO3
iNV YES
iNV NO
0......9
→
Choose the operating, inverted or not inverted, of the relay output.
DEL. = 000
→
Enter the time delay before the valve is opened (value between 0 and
200 s).
→
Confirm.
Figure 82:
Configuring the DO2 relay output
→
If you do not want to adjust another parameter, go to the "END" parameter of the Parameters menu and press
ENTER
to save the settings or not and go back to the Process level.
English
Type 8025 - 8035 BATCH