Motor

Data

Parameter group related to setting motor data in the drive.

3.6.1 P-0# Motor Data

Parameters to configure Motor, Auto Tuning and Slip
Compensation.

P-01 Motor Poles

Range:

Function:

4

*

[2 - 100]

Enter the number of motor poles.

Poles

~n

n

@ 50 Hz

~n

n

@ 60 Hz

2

2700-2880

3250-3460

4

1350-1450

1625-1730

6

700-960

840-1153

Table 3.13

Table 3.15 shows the number of poles for normal speed
ranges of various motor types. Define motors designed for
other frequencies separately. The motor pole value is
always an even number, because it refers to the total
number of poles, not pairs of poles. The frequency
converter creates the initial setting of P-01 Motor Poles
based on F-04 Base Frequency and P-06 Base Speed.

P-02 Motor Power [HP]

Range:

Function:

4.00

hp

*

[0.09 -

3000.00 hp]

Enter the nominal motor power in HP

according to the motor nameplate data.

The default value corresponds to the

nominal rated output of the unit. This

parameter is visible in keypad if

K-03 Regional Settings is [1] US

P-03 Motor Current

Range:

Function:

7.20 A

*

[0.10 - 10000.00

A]

Enter the nominal motor current

value from the motor nameplate

data. The data are used for

calculating torque, motor protection

etc.

P-04 Auto Tune

Option:

Function:

NOTE

This parameter cannot be adjusted while
the motor is running.

The Auto Tune function optimises dynamic

motor performance by automatically

optimising the advanced motor parameters

P-04 Auto Tune

Option:

Function:

(P-30 Stator Resistance (Rs) to P-35 Main

Reactance (Xh)) at motor standstill.

Activate the Auto Tune function by pressing

[Hand] after selecting [1] or [2] Reduced Auto

Tune. After a normal sequence, the display will

read: "Press [OK] to finish Auto Tune". After

pressing the [OK] key the frequency converter

is ready for operation.

[0]

*

Off

[1]

Full Auto

Tune

Performs Auto Tune of the stator resistance R

S

,

the rotor resistance R

r

, the stator leakage

reactance X

1

, the rotor leakage reactance X

2

and the main reactance X

h

. Do not select this

option if an LC filter is used between the

frequency converter and the motor.

[2]

Reduced

Auto Tune

Performs a reduced Auto Tune of the stator

resistance R

s

in the system only.

Note:

For the best results run Auto Tune on a cold
motor.

Auto Tune cannot be performed while the motor
is running.

Auto Tune cannot be performed on permanent
magnet motors.

NOTE

It is important to set motor parameters F-04, F-05, and
P-02 to P-08 correctly, since these form part of the Auto
Tune algorithm. An Auto Tune should be performed to
achieve optimum dynamic motor performance. It may take
up to 10 min, depending on the power rating of the
motor.

NOTE

Avoid generating external torque during Auto Tune.

NOTE

If one of the settings in parameters F-04, F-05, or P-02 to
P-08 is changed, P-30 Stator Resistance (Rs) to P-01 Motor
Poles
,
the advanced motor parameters, will return to
default setting.

NOTE

Auto Tune will work problem-free on 1 motor size down,
typically work on 2 motor sizes down, rarely work on 3
sizes down and never work on 4 sizes down. Keep in mind
that the accuracy of the measured motor data will be
poorer when operating on motors smaller than nominal
drive size.

Parameter Descriptions

AF-650 GP Programming Guide

56

DET-618C