beautypg.com

GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual

Page 16

background image

press [OK]. Information is displayed about the condition of
the frequency converter before it enters the alarm mode.

[Back]
reverts to the previous step or layer in the navigation
structure.

[Cancel]
last change or command will be cancelled as long as the
display has not been changed.

[Info]
supplies information about a command, parameter, or
function in any display window. [Info] provides detailed
information whenever help is needed.
Exit info mode by pressing either [Info], [Back], or [Cancel].

Illustration 2.5 Back

Illustration 2.6 Cancel

Illustration 2.7 Info

Navigation Keys
The four navigation keys are used to navigate between the
different choices available in [Quick Menu], [Main Menu]
and [Alarm Log]. Use the keys to move the cursor.

[OK]
is used for choosing a parameter marked by the cursor
and for enabling the change of a parameter.

Local Control Keys
for local control are found at the bottom of the keypad.

Illustration 2.8 Local Control Keys

[Hand]
enables control of the frequency converter via the keypad.
[Hand ] also starts the motor, and it is now possible to
enter the motor speed data by means of the arrow keys.
The key can be selected as [1] Enable or [0] Disable via
K-40 [Hand] Button on Keypad
External stop signals activated by means of control signals
or a serial bus will override a “start” command via the
keypad.
The following control signals will still be active when
[Hand ] is activated

[Hand] - [Off] - [Auto]

Reset

Coasting stop inverse

Reversing

Set-up select bit 0- Set-up select bit 1

Stop command from serial communication

Quick stop

DC brake

[Off]
stops the connected motor. The key can be selected as [1]
Enable
or [0] Disable via K-41 [Off] Button on Keypad. If no
external stop function is selected and the [Off] key is
inactive the motor can be stopped by disconnecting the
voltage.

[Auto]
enables the frequency converter to be controlled via the
control terminals and/or serial communication. When a
start signal is applied on the control terminals and/or the
bus, the frequency converter will start. The key can be
selected as [1] Enable or [0] Disable via K-42 [Auto] Button
on Keypad
.

NOTE

An active HAND-OFF-AUTO signal via the digital inputs has
higher priority than the control keys [Hand] – [Auto].

[Reset]
is used for resetting the frequency converter after an alarm
(trip). It can be selected as [1] Enable or [0] Disable via
K-43 [Reset] Button on Keypad.

The parameter shortcut can be carried out by holding
down the [Main Menu] key for 3 seconds. The parameter
shortcut allows direct access to any parameter.

How to Program

AF-650 GP Programming Guide

DET-618C

15

2

2