2.1.17 Restoring Drive to Factory Settings
The drive can be restored to factory settings in two ways.
Recommended
1.
Select H-03 Restore Factory Settings
2.
Press [OK]
3.
Select [2] Restore Factory Settings
4.
Press [OK]
5.
Cut off the mains supply and wait until the
display turns off.
6.
Reconnect the mains supply - the frequency
converter is now reset.
H-03 Restore Factory Settings restores all except:
SP-50 RFI Filter
O-31 Address
O-37 Max Inter-Char Delay
ID-00 Operating hours to ID-05 Over Volt's
ID-20 Historic Log: Event to ID-22 Historic Log:
Time
ID-30 Fault Log: Error Code to ID-32 Alarm Log:
Time
Manual Restore of Factory Settings
1.
Disconnect from mains and wait until the display
turns off
2.
Press [Status] - [Main Menu] - [OK] at the same
time while power up for keypad
3.
Release the keys after 5 s.
4.
The frequency converter is now programmed
according to default settings.
Manual restores all except:
ID-00 Operating hours
ID-03 Power Up's
ID-04 Over Temp's
ID-05 Over Volt's
NOTE
A manual restore also resets serial communication, RFI
filter settings (SP-50 RFI Filter) and fault log settings.
How to Program
AF-650 GP Programming Guide
22
DET-618C
2