2 id-1# data trending settings – GE Industrial Solutions AF-650 GP General Purpose Drive Programming Guide User Manual
Page 110
NOTE
The reset is carried out by pressing [OK].
ID-07 Reset Running Hours Counter
Option:
Function:
[0]
*
Do not reset
[1]
Reset counter Select [1] Reset and press [OK] to reset the
Running Hours counter to zero (see
ID-01 Running Hours). This parameter cannot
be selected via the serial port, RS-485.
Select [0] Do not reset if no reset of the
Running Hours counter is desired.
ID-08 Number of Starts
Range:
Function:
0
*
[0 - 2147483647] This is a read out parameter only. The
counter shows the numbers of starts and
stops caused by a normal Start/Stop
command and/or when entering/leaving
sleep mode.
NOTE
This parameter will be reset when resetting ID-07 Reset
Running Hours Counter.
3.17.2 ID-1# Data Trending Settings
Data Log Settings enables continous logging of up to 4
data sources (ID-10 Trending Source) at individual rates
(ID-11 Trending Interval). A trigger event (ID-12 Trigger
Event) and window (ID-14 Samples Before Trigger) are used
to start and stop the logging conditionally.
ID-10 Trending Source
Array [4]
Option:
Function:
Select which variables are
to be logged.
[0]
*
None
[515]
Readout: actual setup
[1200] Control Word
[1201] Reference [Unit]
[1202] Reference %
[1203] Status Word
[1210] Power [kW]
[1211] Power [hp]
[1212] Motor Voltage
[1213] Frequency
[1214] Motor current
[1216] Torque [Nm]
[1217] Speed [RPM]
[1218] Motor Thermal
[1221] Torque [%] High Res.
[1222] Torque [%]
ID-10 Trending Source
Array [4]
Option:
Function:
[1225] Torque [Nm] High
[1230] DC Link Voltage
[1232] Brake Energy /s
[1233] Brake Energy /2 min
[1234] Heatsink Temp.
[1235] Drive Thermal
[1248] Speed Ref. After Ramp [RPM]
[1250] External Reference
[1251] Pulse Reference
[1252] Feedback[Unit]
[1257] Feedback [RPM]
[1260] Digital Input
[1262] Analog Input 53
[1264] Analog Input 54
[1265] Analog Output 42 [mA]
[1266] Digital Output [bin]
[1275] Analog In X30/11
[1276] Analog In X30/12
[1277] Analog Out X30/8 [mA]
[1290] Alarm Word
[1292] Warning Word
[1294] Ext. Status Word
ID-11 Trending Interval
Array [4]
Range:
Function:
0.000
*
[0.000 - 0.000] Enter the interval in milliseconds
between each sampling of the variables
to be logged.
ID-12 Trigger Event
Select the trigger event. When the trigger event occurs, a
window is applied to freeze the log. The log will then retain a
specified percentage of samples before the occurrence of the
trigger event (ID-14 Samples Before Trigger).
Choices are described under E-## Digital Output.
Option:
Function:
[0]
*
False
[1]
True
[2]
Running
[3]
In range
[4]
On reference
[5]
Torque limit
[6]
Current Limit
[7]
Out of current range
[8]
Below I low
[9]
Above I high
[10]
Out of speed range
[11]
Below speed low
[12]
Above speed high
[13]
Out of feedb. range
Parameter Descriptions
AF-650 GP Programming Guide
DET-618C
109
3