2.1.2 Quick Transfer of Parameter Settings

between Multiple Frequency
Converters

Once the set-up of a frequency converter is complete,
store the data in the keypad or on a PC via Drive Control
Tool Software DCT 10.

Illustration 2.9 Keypad

Data storage in keypad

NOTE

Stop the motor before performing this operation.

1.

Go to K-50 Keypad Copy

2.

Press the [OK] key

3.

Select “All to keypad”

4.

Press the [OK] key

All parameter settings are now stored in the keypad
indicated by the progress bar. When 100% is reached,
press [OK].

Connect the keypad to another frequency converter and
copy the parameter settings to this frequency converter as
well.

Data transfer from keypad to frequency converter

NOTE

Stop the motor before performing this operation.

1.

Go to K-50 Keypad Copy

2.

Press the [OK] key

3.

Select “All from keypad”

4.

Press the [OK] key

The parameter settings stored in the keypad are now
transferred to the frequency converter indicated by the
progress bar. When 100% is reached, press [OK].

2.1.3 Display Mode

In normal operation, up to 5 different operating variables
can be indicated continuously in the middle section: 1.1,
1.2, and 1.3 as well as 2 and 3.

2.1.4 Display Mode - Selection of Read-

Outs

It is possible to toggle between three status read-out
screens by pressing [Status].
Operating variables with different formatting are shown in
each status screen - see below.

Table 2.1 shows the measurements that can be linked to
each of the operating variables. When options are
mounted, additional measurements are available. Define
the links via K-20 Display Line 1.1 Small, K-21 Display Line
1.2 Small
, K-22 Display Line 1.3 Small, K-23 Display Line 2
Large
, and K-24 Display Line 3 Large.

Each readout parameter selected in K-20 Display Line 1.1
Small
to K-24 Display Line 3 Large has its own scale and
digits after a possible decimal point. By larger numeric
value of a parameter fewer digits are displayed after the
decimal point.
Ex.: Current readout 5.25A; 15.2A 105A.

Operating variable

Unit

DR-00 Control Word

hex

DR-01 Reference [Unit]

[unit]

DR-02 Reference [%]

%

DR-03 Status Word

hex

DR-05 Main Actual Value [%]

%

DR-10 Power [kW]

[kW]

DR-11 Power [hp]

[HP]

DR-12 Motor Voltage

[V]

DR-13 Frequency

[Hz]

DR-14 Motor current

[A]

DR-16 Torque [Nm]

Nm

DR-17 Speed [RPM]

[RPM]

DR-18 Motor Thermal

%

How to Program

AF-650 GP Programming Guide

16

DET-618C

2

2