Operating Manual

137

Power Supply Concept

Power Supply Units

V

CAUTION!

Because of chassis airflow disruption, the power supply unit slot should
not be vacant and/or uncovered for more than five minutes when the
system power is ON. Exceeding the five-minute limit may damage com-
ponents.

Each PSU dummy module includes three fans respectively.

There is one LED indicator (1 on

figure 80

) on the front of the PSU dummy

module for monitoring the status of built-in fans.

Figure 80: PSU dummy module

If you want to install an additional power supply unit, you must first remove the
PSU dummy module from the corresponding slot.

Ê

Remove the PSU dummy module from the corresponding slot.

Removal/installation is the same as for the power supply unit (see

section

“Replacing a Power Supply Unit” on page 133

).

V

CAUTION!

Keep the dummy module for future use. If you remove a power supply
unit and do not replace it with a new one, you must reinstall the
dummy module.

Ê

Insert the additional power supply unit in the corresponding slot and connect
it to the mains.

1