ROTARY GEAR PUMP

ELECTRONIC FOAM PROPORTIONING SYSTEM

Section

II

: Installation

concentrate level is not restored the
Hale FoamLogix system will shut down.
When locating the side mount low tank

Figure 2-24. Control Unit Cable Connection

Figure 2-23. Distribution Box Connections

LOW TANK SENSOR

CONNECTION **

(WHEN SINGLE TANK OR MST

OPTION IS ORDERED A KIT

WITH THE MATING PACKARD

CONNECTOR IS INCLUDED.)

PRIMARY POWER CONNECTION

(60 AMPS MINIMUM) *

USE MINIMUM 4 AWG TYPE SGX (SAE J1127) BATTERY CABLE

FOR CABLE LENGTH UP TO 6 FEET.

FOR CABLE LENGTH OVER 6 FEET REFER TO TABLE 2-2 FOR

PROPER GAUGE WIRE

.

(Use Silicon Sealant to Prevent Corrosion and

use Rubber Boot Provided to Prevent Short

Circuit)

CONTROL UNIT

CABLE CONNECTION

(6-PIN) *

POS (+) MOTOR

TERMINAL

ACCESSORY CONNECTOR

(Plug inserted at factory when single tank installed.)

(Connection made at factory when Hale MDT

II

or Hale ADT option installed.)

(Field connection required at installation when Hale MST option installed.)

*

CONNECTION MADE DURING SYSTEM INSTALLATION.

**

CONNECTION REQUIRED WHEN SINGLE TANK OR
HALE MST INSTALLED.

NEG (-) MOTOR

TERMINAL

FEEDBACK

SENSOR PIGTAIL

CHASSIS GROUND STRAP CONNECTION *

USE 1-¼ INCH WIDE FLAT BRAIDED GROUND STRAP MAXIMUM

18 INCHES (457 mm) LONG

(Use Silicon Sealant to Prevent Corrosion)

level sensor on the foam tank sufficient
foam concentrate should be present for
one minute of operation at rated flow.

FLOWSENSOR

(10, 20 OR 30 FEET LONG)

CONTROL CABLE

TO DISTRIBUTION BOX

(6 FEET LONG)

REMOTE ACTUATION

SWITCH

(20 INCHES LONG)

CAN CONNECTION

(20 INCHES LONG)

(FOR CAFSPro

INSTALLATIONS ONLY)

BACK OF CONTROL UNIT

14 PIN AMP CONNECTOR

CONNECTS TO BACK OF

FoamLogix CONTROL UNIT

DISPLAY POWER GROUND

CONNECTION

(12 INCHES LONG)

RED=POWER; BLACK=GND