Ιι -35 – Hale 5.0 FoamLogix User Manual
Page 65
![background image](/manuals/545157/65/background.png)
ΙΙ
-35
ROTARY GEAR PUMP
ELECTRONIC FOAM PROPORTIONING SYSTEM
Section
II
: Installation
concentrate level is not restored the
Hale FoamLogix system will shut down.
When locating the side mount low tank
Figure 2-24. Control Unit Cable Connection
Figure 2-23. Distribution Box Connections
LOW TANK SENSOR
CONNECTION **
(WHEN SINGLE TANK OR MST
OPTION IS ORDERED A KIT
WITH THE MATING PACKARD
CONNECTOR IS INCLUDED.)
PRIMARY POWER CONNECTION
(60 AMPS MINIMUM) *
USE MINIMUM 4 AWG TYPE SGX (SAE J1127) BATTERY CABLE
FOR CABLE LENGTH UP TO 6 FEET.
FOR CABLE LENGTH OVER 6 FEET REFER TO TABLE 2-2 FOR
PROPER GAUGE WIRE
.
(Use Silicon Sealant to Prevent Corrosion and
use Rubber Boot Provided to Prevent Short
Circuit)
CONTROL UNIT
CABLE CONNECTION
(6-PIN) *
POS (+) MOTOR
TERMINAL
ACCESSORY CONNECTOR
(Plug inserted at factory when single tank installed.)
(Connection made at factory when Hale MDT
II
or Hale ADT option installed.)
(Field connection required at installation when Hale MST option installed.)
*
CONNECTION MADE DURING SYSTEM INSTALLATION.
**
CONNECTION REQUIRED WHEN SINGLE TANK OR
HALE MST INSTALLED.
NEG (-) MOTOR
TERMINAL
FEEDBACK
SENSOR PIGTAIL
CHASSIS GROUND STRAP CONNECTION *
USE 1-¼ INCH WIDE FLAT BRAIDED GROUND STRAP MAXIMUM
18 INCHES (457 mm) LONG
(Use Silicon Sealant to Prevent Corrosion)
level sensor on the foam tank sufficient
foam concentrate should be present for
one minute of operation at rated flow.
FLOWSENSOR
(10, 20 OR 30 FEET LONG)
CONTROL CABLE
TO DISTRIBUTION BOX
(6 FEET LONG)
REMOTE ACTUATION
SWITCH
(20 INCHES LONG)
CAN CONNECTION
(20 INCHES LONG)
(FOR CAFSPro
INSTALLATIONS ONLY)
BACK OF CONTROL UNIT
14 PIN AMP CONNECTOR
CONNECTS TO BACK OF
FoamLogix CONTROL UNIT
DISPLAY POWER GROUND
CONNECTION
(12 INCHES LONG)
RED=POWER; BLACK=GND