4 obtaining external pressure and temperature data, Obtaining external pressure and temperature data, Section 9.4 – Emerson Process Management MICRO MOTION 2400S User Manual
Page 95: See section 9.4, Vicenet tool, see figure 9-4

Configuration and Use Manual
87
Pressure Compensation and Temperature Compensation
Me
asu
reme
nt P
er
form
anc
e
Defaults
T
rou
b
lesho
o
ti
ng
Compensation
Figure 9-4
Configuring external temperature compensation with a DeviceNet tool
9.4
Obtaining external pressure and temperature data
The DeviceNet output assemblies used to obtain external pressure and/or temperature data are listed
in Table 9-1. Use standard DeviceNet methods to implement the required connection.
Table 9-1
Output assemblies used for pressure or temperature compensation
Instance ID
Data description
Size
Bytes
Data type
50
External pressure
4 bytes
Bytes 0–3
REAL
51
External temperature
4 bytes
Bytes 0–3
REAL
52
External pressure
External temperature
8 bytes
Bytes 0–3
Bytes 4–7
REAL
REAL
Enable temperature
compensation
Class: Calibration Object (0x65)
Instance: 1
Attribute ID: 25
Data type: BOOL
Value:
· 0 = disabled
· 1 = enabled
Set temperature unit
Class: Analog Input Point Object (0x0A)
Instance: 4
Attribute ID: 102
Value: See Table 6-6
Service: Set
Yes
Use static
temp value?
No
Set up output
assembly
(2)
Class: Calibration Object (0x65)
Instance: 1
Attribute ID: 26
Data type: REAL
Service: Set
Set static value
(1) Temperature measurement unit
must be configured to match
temperature unit used by
external device. See
Section 6.3.
(2) See Section 9.4.