C.3 gas standard volume object (0x64), Gas standard volume object (0x64), D c-5 – Emerson Process Management MICRO MOTION 2400S User Manual
Page 154: H c-5 and, See table c-4, See table c-5
![background image](/manuals/82275/154/background.png)
146
Micro Motion
®
Model 2400S Transmitters for DeviceNet
™
Device Profile
C.3
Gas Standard Volume Object (0x64)
104
Damping
REAL
Set
NV
Density damping value
Unit = seconds
105
Cutoff
REAL
Set
NV
Value below which density
will be reported as 0
106
Meter factor
REAL
Set
NV
A multiplier to the
calculated density
Table C-4
Analog Input Point Object (0x0A) – Instance 4 (temperature)
Attrib
ID
Name
Data type
Service
Mem
Description
Comments
3
Value
REAL
Get
V
Current value of
temperature process
variable
Based on Attribute 8
4
Status
BOOL
Get
V
Point status
• 0 = Good
• 1 = Alarm state
8
Value data type
USINT
Get
V
Data type used to report
mass flow process
variable
• 1 = REAL
102
Value
engineering
units
UINT
Set
NV
Temperature
measurement unit
See Table 6-6 for unit
codes.
104
Damping
REAL
Set
NV
Temperature damping
value
Unit = seconds
Table C-5
Gas Standard Volume Object (0x64) – Instance 1
Attrib
ID
Name
Data type
Service
Mem
Description
Comments
1
Gas standard
volume flow
REAL
Get
V
Current value of gas
standard volume flow
process variable
2
Gas standard
volume total
REAL
Get
Reset
(1)
V
Current value of gas
standard volume total
3
Gas standard
volume
inventory
REAL
Get
Reset
(2)
V
Current value of gas
standard volume
inventory
4
Reference
density
REAL
Set
NV
Reference density of gas
being measured
5
Gas standard
volume flow
units
UINT
Set
NV
Gas standard volume flow
measurement unit
See Table 6-4 for unit
codes.
6
Gas standard
volume total and
inventory units
UINT
Get
V
Gas standard volume total
and inventory units
Transmitter
automatically
determines this based
on Attribute 102.
See Table C-14 for unit
codes.
Table C-3
Analog Input Point Object (0x0A) – Instance 3 (density) continued
Attrib
ID
Name
Data type
Service
Mem
Description
Comments