8 Troubleshooting
8.1.2 Troubleshooting of Alarms
8-22
A.E63:
MECHATROLINK
Synchronization
Frame Not Received
Alarm
MECHATROLINK wiring is
incorrect.
Check the MECHATROLINK wir-
ings.
Correct the MECHATROLINK wir-
ing.
MECHATROLINK data recep-
tion error occurred due to noise
interference.
−
Take measures against noise. Check
the MECHATROLINK communi-
cations cable and FG wiring and
take measures such as adding ferrite
core on the MECHATROLINK
communications cable.
A SERVOPACK fault occurred.
−
Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.
A.E71:
Safety Option Module
Detection Failure
The connection between the
SERVOPACK and the safety
option module is faulty.
Check the connection between the
SERVOPACK and the safety option
module.
Correctly connect the safety option
module.
The safety option module was
disconnected.
–
Execute Fn014 (Resetting configu-
ration error of option module) with
using the digital operator or Sig-
maWin+ and turn the power supply
OFF and then ON again.
A safety option module fault
occurred.
–
Replace the safety option module.
A SERVOPACK fault occurred.
–
Replace the SERVOPACK.
A.E74:
Unsupported Safety
Option Module
A safety option module fault
occurred.
−
Replace the safety option module.
A unsupported safety option
module was connected.
Refer to the catalog of the con-
nected safety option module.
Connect a compatible safety option
module.
A.E75:
Unsupported
Feedback Option
Module
A feedback option module fault
occurred.
−
Replace the feedback option mod-
ule.
A unsupported feedback option
module was connected.
Refer to the catalog of the con-
nected feedback option module or
the manual of the SERVOPACK.
Connect a compatible feedback
option module.
A.EA2:
DRV Alarm 2
(SERVOPACK WDT
error)
MECHATROLINK transmission
cycle fluctuated.
Check the MECHATROLINK
transmission cycle setting.
Remove the cause of transmission
cycle fluctuation at host controller.
A SERVOPACK fault occurred.
−
Turn the power supply OFF and
then ON again. If the alarm still
occurs, the SERVOPACK may be
faulty. Replace the SERVOPACK.
A.Eb1:
Safety Function Signal
Input Timing Error
The lag between activations of
the input signals /HWBB1 and
/HWBB2 for the HWBB function
is ten second or more.
Measure the time lag between the /
HWBB1 and
/HWBB2 signals.
The output signal circuits or devices
for /HWBB1 and
/HWBB2 or the SERVOPACK
input signal circuits may be faulty.
Alternatively, the input signal
cables may be disconnected. Check
if any of these items are faulty or
have been disconnected.
A.Ed1:
Command Execution
Timeout
A timeout error occurred when
using an MECHATROLINK
command.
Check the motor status when the
command is executed.
Execute the SV_ON or SENS_ON
command only when the motor is
not running.
Check the status of the linear scale
after an output is made to execute
the command.
Execute the SENS_ON command
only when a linear scale is con-
nected.
(cont’d)
Alarm Number:
Alarm Name
(Alarm Description)
Cause
Investigative Actions
Corrective Actions