3) setting monitor factor – Yaskawa Sigma-5 User Manual: Design and Maintenance - Linear Motors MECHATROLINK-III Communications Reference User Manual
Page 156

5 Adjustments
5.1.3 Monitoring Operation during Adjustment
5-6
The following signals can be monitored by selecting functions with parameters Pn006 and Pn007.
Pn006 is used for analog monitor 1 and Pn007 is used for analog monitor 2.
∗ Refer to 5.8.1 Switching Gain Settings for details.
(3) Setting Monitor Factor
The output voltages on analog monitors 1 and 2 are calculated by the following equations.
Parameter
Description
Monitor Signal
Unit
Remarks
Pn006
Pn007
n.
00
[Pn007
Factory
Setting]
Motor moving speed
1 V/1000 mm/s
−
n.
01
Speed reference
1 V/1000 mm/s
−
n.
02
[Pn006
Factory
Setting]
Force reference
1 V/100% rated force
−
n.
03
Position error
0.05 V/1 reference unit
0 V at speed/force control
n.
04
Position amplifier error
0.05 V/1 linear scale
pulse unit
Position error after electronic
gear conversion
n.
05
Position reference speed
1 V/1000 mm/s
−
n.
06
Reserved (Do not change.)
−
−
n.
07
Reserved (Do not change.)
−
−
n.
08
Positioning completed
Positioning completed:
5 V
Positioning not com-
pleted: 0 V
Completion indicated by out-
put voltage.
n.
09
Speed feedforward
1 V/1000 mm/s
−
n.
0A
Force feedforward
1 V/100% rated force
−
n.
0B
Active gain
*
1st gain: 1 V
2nd gain: 2 V
Gain type indicated by output
voltage.
n.
0C
Completion of position reference
Completed: 5 V
Not completed: 0 V
Completion indicated by out-
put voltage.
n.
0D
Reserved (Do not change.)
−
−
Analog monitor 1 output voltage = (-1)
×
Signal selection
(Pn006=n.00
غغ) (Pn552)
Analog monitor 2 output voltage = (-1)
×
Signal selection
(Pn007=n.00
غغ)
×
Multiplier + Offset voltage [V]
×
Multiplier + Offset voltage [V]
(Pn550)
(Pn551)
(Pn553)