beautypg.com

SMA SC 500CP-10-JP Installation Manual User Manual

Page 85

background image

SMA Solar Technology AG

17  Technical Data

Installation Manual

SCCP-JP-IA-A4-en-12

85

Efficiency (measured without internal power supply)*

* For order option "Noise reduction", the values change (see datasheet).

Max. efficiency / European weighted efficiency /

CEC weighted efficiency

98.6% / 98.4% / 98.5%

Protective Devices
Input-side disconnection point

Motor-driven DC load-break switch

AC disconnection point

AC circuit breaker

DC overvoltage protection

Surge arrester type I

Lightning protection (as per IEC 62305-1)

Lightning protection level III

Grid monitoring

Standard features

Islanding detection

active / passive (optional)

Ground fault monitoring / remote ground fault monitoring

optional / optional

Insulation monitoring

optional

Surge arrester for communication interface /

string-current monitoring

optional / optional

Surge arrester for auxiliary power supply

Surge arrester type I and type II

Protection class (as per IEC 62103) /

overvoltage category (as per IEC 60664-1)

I / III

General Data
Dimensions (width x height x depth)

2,562 mm / 2,272 mm / 956 mm***

Weight***

approx. 1,800 kg

Operating temperature range

− 25°C to +62°C

Noise emission*

* Sound pressure level at a distance of 10 m

61 db(A)***

*** For order option "Noise reduction", the values change (see datasheet).

Max. self-consumption (operation)** /

self-consumption (night)

** Self-consumption at rated operation

1,900 W / < 100 W

External auxiliary supply voltage

230 / 400 V (3/N/PE)

Cooling concept

Opticool

Degree of protection: electronics / connection area

(as per IEC 60529)

IP54 / IP43

Application

In unprotected outdoor environments

Maximum permissible value for relative humidity

(non-condensing)

15% to 95%

Maximum operating altitude above MSL

2,000 m

Fresh air consumption

3,000 m

3

/h