SMA Solar Technology AG
12 Cable Connection of External Devices and Connections in the Interface Cabinet
Installation Manual
SCCP-JP-IA-A4-en-12
59
3. Release the three screws at the side of the sealing plate.
4. Remove the required number of rubber seals from the sealing plate. Make sure that the diameter of the rubber seals
corresponds to the diameter of the cables to be inserted. Use the additional rubber seals included in the scope of
delivery if necessary.
5. Remove the sealing plugs from the rubber seals.
6. Lead the cables through the rubber seals.
7. Insert the rubber seals in the sealing plate avoiding any distortion. This will guarantee a tight fit.
8. Tighten the screws at the side of the sealing plate.
9. Screw the sealing plate to the floor of the interface cabinet.
12.3 Connecting the Cables in the Interface Cabinet
12.3.1 Connecting the Cables to the Connecting Terminal Plate
1. Dismantle the cable by 60 mm.
2. Strip off the insulation of the insulated conductors by 5 mm.
3. Connect the cable in accordance with the circuit diagram.
• Remove the connection plug from the base terminal.