15  Commissioning

SMA Solar Technology AG

74

SCCP-JP-IA-A4-en-12

Installation Manual

15.4 Mounting the Protective Covers

Figure 29: Position of the protective covers in the Sunny Central

Procedure:

1. Make sure that all cables are attached to the cable support rails with cable ties.
2. Tighten all protective covers (torque: 5 Nm).

15.5 Checking the Voltages on the Sunny Central

15.5.1 Checking the DC Voltages

Position

Designation

A

Protective cover

B

Protective cover for the order option "EMC filtering device"

'$1*(5

Danger to life due to electric arcs if the multimeter is not connected correctly
Contacting the measurement points incorrectly can cause an electric arc. Electric arcs result in death or serious injury.

• Select the appropriate measurement range on the multimeter.
• Wear personal protective equipment.
• Select the correct measurement points.