9  Grounding Terminal

SMA Solar Technology AG

42

SCCP-JP-IA-A4-en-12

Installation Manual

9 Grounding Terminal

9.1 Cable and Terminal Lug Requirements

Cables:

☐ Use copper or aluminum cables only.
☐ Maximum cable cross-section: 400 mm

2

Terminal lugs:

☐ Only use tin-plated terminal lugs.
☐ Only use the nuts, screws and washers included in the scope of delivery for the connection.
☐ Always connect two-hole terminal lugs with two screws.
☐ The terminal lugs must be designed for temperatures of at least +95°C.
☐ The width of the terminal lugs must exceed the washer diameter (32 mm). This will ensure that the defined torques

are effective over the whole surface.

9.2 Grounding

Figure 16: Connecting with one terminal lug

Equipotential bonding

• Ground the Sunny Central in accordance with the applicable regulations.

Position

Designation

A

Nut

B

Spring washer

C

Fender washer

D

Busbar