10  DC Connection

SMA Solar Technology AG

50

SCCP-JP-IA-A4-en-12

Installation Manual

10.3 DC Connection with DC Busbar Option

10.3.1 Cable and Terminal Lug Requirements

Cables:

☐ Use copper or aluminum cables only.
☐ Maximum cable cross-section: 400 mm

2

Terminal lugs:

☐ Use tin-plated terminal lugs only.
☐ Only use the nuts, screws and washers included in the scope of delivery for the connection.
☐ Always connect two-hole terminal lugs with two screws.
☐ The terminal lugs must be designed for temperatures of at least +95°C.
☐ The width of the terminal lugs must exceed the washer diameter (32 mm). This will ensure that the defined torques

are effective over the whole surface.

10.3.2 Connection Area with DC Busbar Option

Figure 20: Dimensions of the DC busbar (example)

Position

Designation

A

Grounding busbar

B

Connection bracket for DC‒ cable

C

Connection bracket for DC+ cable

D

Connection bracket for AC cable