beautypg.com

2 sunny central 630cp‑jp – SMA SC 500CP-10-JP Installation Manual User Manual

Page 82

background image

17  Technical Data

SMA Solar Technology AG

82

SCCP-JP-IA-A4-en-12

Installation Manual

17.2 Sunny Central 630CP‑JP

Certificates and approvals (more available upon request)

EN 61000-6-2, EN 61000-6-4, CE conformity,

EEG conformity, BDEW-MSRL /

JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0 (2011)*,

Arrêté du 23/04/08, R.D. 1663 /

2000, R.D. 661 / 2007

Type designation

SC 500CP-10-JP

* Type-tested by the manufacturer in accordance with JET (Japan Electrical Safety & Environment Technology Laboratories Foundation)

Input (DC)
Max. DC power (@ cos φ =1)

713 kW

Max. input voltage

1,000 V

MPP voltage range (50 Hz) / MPP voltage range (60 Hz)

500 V to 850 V* / 505 V to 850 V*

* At 1.05 V

AC, nom

and cos φ = 1 and nominal power P

nom

DC voltage range (50 Hz) / DC voltage range (60 Hz)

500 V to 850 V / 500 V to 850 V

Rated input voltage

529 V

Max. input current

1,350 A

V

mpp min

at I

mpp

< I

DCmax

500 V (50 Hz) / 500 V (60 Hz)

Number of independent MPP inputs

1

Number of DC inputs

9

Output (AC)
Rated power (at 25°C) / nominal AC power (at 50°C)

700 kVA

630 kVA*

* For order option "Noise reduction", the values change (see datasheet).

Nominal AC voltage/range

315 V / 284 V to 362 V

AC power frequency / range

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated power frequency / rated grid voltage

50 Hz / 315 V

Max. output current

1,283 A

Max. total harmonic distortion

< 3%

Power factor at rated power / displacement power factor

adjustable

1 / 0.9 overexcited to 0.9 underexcited

Feed-in phases / connection phases

3 / 3

Efficiency (measured without internal power supply)*

* For order option "Noise reduction", the values change (see datasheet).

Max. efficiency / European weighted efficiency /

CEC weighted efficiency

98.7% / 98.5% / 98.5%

Equipment