2 sunny central 630cp‑jp – SMA SC 500CP-10-JP Installation Manual User Manual
Page 82

17 Technical Data
SMA Solar Technology AG
82
SCCP-JP-IA-A4-en-12
Installation Manual
17.2 Sunny Central 630CP‑JP
Certificates and approvals (more available upon request)
EN 61000-6-2, EN 61000-6-4, CE conformity,
EEG conformity, BDEW-MSRL /
JETGR0002-1-2.0 (2011) / JETGR0003-1-2.0 (2011)*,
Arrêté du 23/04/08, R.D. 1663 /
2000, R.D. 661 / 2007
Type designation
SC 500CP-10-JP
* Type-tested by the manufacturer in accordance with JET (Japan Electrical Safety & Environment Technology Laboratories Foundation)
Input (DC)
Max. DC power (@ cos φ =1)
713 kW
Max. input voltage
1,000 V
MPP voltage range (50 Hz) / MPP voltage range (60 Hz)
500 V to 850 V* / 505 V to 850 V*
* At 1.05 V
AC, nom
and cos φ = 1 and nominal power P
nom
DC voltage range (50 Hz) / DC voltage range (60 Hz)
500 V to 850 V / 500 V to 850 V
Rated input voltage
529 V
Max. input current
1,350 A
V
mpp min
at I
mpp
< I
DCmax
500 V (50 Hz) / 500 V (60 Hz)
Number of independent MPP inputs
1
Number of DC inputs
9
Output (AC)
Rated power (at 25°C) / nominal AC power (at 50°C)
700 kVA
630 kVA*
* For order option "Noise reduction", the values change (see datasheet).
Nominal AC voltage/range
315 V / 284 V to 362 V
AC power frequency / range
50 Hz, 60 Hz / 47 Hz to 63 Hz
Rated power frequency / rated grid voltage
50 Hz / 315 V
Max. output current
1,283 A
Max. total harmonic distortion
< 3%
Power factor at rated power / displacement power factor
adjustable
1 / 0.9 overexcited to 0.9 underexcited
Feed-in phases / connection phases
3 / 3
Efficiency (measured without internal power supply)*
* For order option "Noise reduction", the values change (see datasheet).
Max. efficiency / European weighted efficiency /
CEC weighted efficiency
98.7% / 98.5% / 98.5%
Equipment