2  Safety

SMA Solar Technology AG

8

SCCP-JP-IA-A4-en-12

Installation Manual

2 Safety

2.1 Intended Use

The Sunny Central is a PV inverter which converts the direct current generated in the PV modules into grid-compliant

alternating current. An external MV transformer fitted downstream feeds the generated alternating current into the utility

grid.
The Sunny Central is suitable for outdoor installation provided that the specified safety distances are maintained.

The Sunny Central for station installation is suitable exclusively for indoor installation provided that the specified safety

distances are maintained. The enclosure conforms with degree of protection IP54. The Sunny Central is classified under

Class 4C2 as per EN 60721-3-4 and is suitable for operation in a chemically active environment.
The maximum permissible DC input voltage of the Sunny Central must not be exceeded.
The Sunny Central must only be operated in conjunction with a suitable MV transformer. The MV transformer must be

designed for voltages that arise during pulsed mode of the Sunny Central. The maximum AC voltages to ground are as

follows:

• The voltages can reach a maximum of ±800 V to ground for the inverter type SC 500CP-JP.
• The voltages can reach a maximum of ±1,450 V to ground for the inverter type SC 630CP-JP.
• The voltages can reach a maximum of ±1,450 V to ground for the inverter type SC 800CP-JP.

Do not disconnect or adjust settings that affect grid management services without first obtaining approval from the grid

operator.
Alterations to the product, e.g. modifications or conversions, are only permitted with the express written permission of

SMA Solar Technology AG. Making unauthorized changes will void the warranty and will normally result in invalidation

of the operating permit. SMA Solar Technology AG shall not be held liable for any damage caused by such changes.
Only use the Sunny Central in accordance with the information provided in the enclosed documentation. Any other

application may cause personal injury or property damage.
The enclosed documentation is an integral part of this product. Keep the documentation in a convenient place for future

reference and observe all instructions contained therein.