17 technical data, 1 sunny central 500cp‑jp – SMA SC 500CP-10-JP Installation Manual User Manual
Page 80

17 Technical Data
SMA Solar Technology AG
80
SCCP-JP-IA-A4-en-12
Installation Manual
17 Technical Data
17.1 Sunny Central 500CP‑JP
Input (DC)
Max. DC power (@ cos φ =1)
511 kW
Max. input voltage
600 V
MPP voltage range (50 Hz) / MPP voltage range (60 Hz)
332 V to 600 V*/332 V to 600 V*
* At 1.05 V
AC, nom
and cos φ = 1 and nominal power P
nom
DC voltage range (50 Hz) / DC voltage range (60 Hz)
311 V to 600 V/321 V to 600 V
Rated input voltage
365 V
Max. input current
1,400 A
V
mpp min
at I
mpp
< I
DCmax
311 V (50 Hz) / 321 V (60 Hz)
Number of independent MPP inputs
1
Number of DC inputs
9
Output (AC)
Rated power (at 25°C) / nominal AC power (at 50°C)
500 kVA
455 kVA*
* For order option "Noise reduction", the values change (see datasheet).
Nominal AC voltage/range
205 V / 185 V to 235 V
AC power frequency / range
50 Hz, 60 Hz / 47 Hz to 63 Hz
Rated power frequency / rated grid voltage
50 Hz / 205 V
Max. output current
1,411 A
Max. total harmonic distortion
< 3%
Power factor at rated power /
displacement power factor adjustable
1 / 0.9 overexcited to 0.9 underexcited
Feed-in phases / connection phases
3 / 3
Efficiency (measured without internal power supply)*
* For order option "Noise reduction", the values change (see datasheet).
Max. efficiency / European weighted efficiency /
CEC weighted efficiency
98% / 97.7% / 97.4%
Protective Devices
Input-side disconnection point
Motor-driven DC load-break switch
AC disconnection point
AC circuit breaker
DC overvoltage protection
Surge arrester type I
Lightning protection (according to IEC 62305-1)
Lightning protection level III
Grid monitoring
Standard features
Islanding detection
active / passive (optional)