beautypg.com

17 technical data, 1 sunny central 500cp‑jp – SMA SC 500CP-10-JP Installation Manual User Manual

Page 80

background image

17  Technical Data

SMA Solar Technology AG

80

SCCP-JP-IA-A4-en-12

Installation Manual

17 Technical Data

17.1 Sunny Central 500CP‑JP

Input (DC)
Max. DC power (@ cos φ =1)

511 kW

Max. input voltage

600 V

MPP voltage range (50 Hz) / MPP voltage range (60 Hz)

332 V to 600 V*/332 V to 600 V*

* At 1.05 V

AC, nom

and cos φ = 1 and nominal power P

nom

DC voltage range (50 Hz) / DC voltage range (60 Hz)

311 V to 600 V/321 V to 600 V

Rated input voltage

365 V

Max. input current

1,400 A

V

mpp min

at I

mpp

< I

DCmax

311 V (50 Hz) / 321 V (60 Hz)

Number of independent MPP inputs

1

Number of DC inputs

9

Output (AC)
Rated power (at 25°C) / nominal AC power (at 50°C)

500 kVA

455 kVA*

* For order option "Noise reduction", the values change (see datasheet).

Nominal AC voltage/range

205 V / 185 V to 235 V

AC power frequency / range

50 Hz, 60 Hz / 47 Hz to 63 Hz

Rated power frequency / rated grid voltage

50 Hz / 205 V

Max. output current

1,411 A

Max. total harmonic distortion

< 3%

Power factor at rated power /

displacement power factor adjustable

1 / 0.9 overexcited to 0.9 underexcited

Feed-in phases / connection phases

3 / 3

Efficiency (measured without internal power supply)*

* For order option "Noise reduction", the values change (see datasheet).

Max. efficiency / European weighted efficiency /

CEC weighted efficiency

98% / 97.7% / 97.4%

Protective Devices
Input-side disconnection point

Motor-driven DC load-break switch

AC disconnection point

AC circuit breaker

DC overvoltage protection

Surge arrester type I

Lightning protection (according to IEC 62305-1)

Lightning protection level III

Grid monitoring

Standard features

Islanding detection

active / passive (optional)