beautypg.com

SMA SC 500CP-10-JP Installation Manual User Manual

Page 27

background image

SMA Solar Technology AG

6  Preparation for Installation

Installation Manual

SCCP-JP-IA-A4-en-12

27

6.1.6 Requirements for Cable Routing between MV Transformer and

Sunny Central

☐ The line conductors must be bundled in the three-phase system.
☐ Between the MV transformer and the Sunny Central there must be three separate cable routes for the AC cables,

e.g. cable channels.

☐ A line conductor L1, L2 and L3 must be laid in each cable channel. Ensure that the distance between the cable

bundles is at least double that of the diameter of a cable. This will prevent current imbalances. Furthermore, it is

recommended to execute cabling between inverter and transformer directly on a grounding strap. This measure

further reduces electromagnetic influences.*

Figure 13: Arrangement of AC cables with three cables per line conductor (example)

:$51,1*

Risk of fire due to overheating of cables
Differing cable lengths cause overheating.

• All line conductors from the Sunny Central to the MV transformer must be of the same length.
• The cable length between the connection points must not exceed 15 m.

* For further information, see the Technical Information "Cable Set ‒ Requirements for and Laying of Cables between Sunny Central CP and

Transformer Compact Station" at www.SMA-Solar.com.

Position

Designation

L1

Line conductor L1

L2

Line conductor L2

L3

Line conductor L3

A

Grounding strap