SMA SC 500CP-10-JP Installation Manual User Manual
Page 81

SMA Solar Technology AG
17 Technical Data
Installation Manual
SCCP-JP-IA-A4-en-12
81
Ground fault monitoring / remote ground fault monitoring
optional / optional
Insulation monitoring
optional
Surge arrester for communication interface / string-current
monitoring
optional / optional
Surge arrester for auxiliary power supply
Surge arrester type I and type II
Protection class (as per IEC 62103) /
overvoltage category (as per IEC 60664-1)
I / III
General Data
Dimensions (width x height x depth)
2,562 mm / 2,272 mm / 956 mm***
Weight***
approx. 1,800 kg
Operating temperature range
− 25°C to +62°C
Noise emission*
* Sound pressure level at a distance of 10 m
60 db(A)***
*** For order option "Noise reduction", the values change (see datasheet).
Max. self-consumption (operation)** /
self-consumption (night)
** Self-consumption at rated operation
1,900 W / < 100 W
External auxiliary supply voltage
230 V / 400 V (3/N/PE)
Cooling concept
Opticool
Degree of protection: electronics / connection area
(as per IEC 60529)
IP54 / IP43
Application
In unprotected outdoor environments
Maximum permissible value for relative humidity
(non-condensing)
15% to 95%
Maximum operating altitude above MSL
2,000 m
Fresh air consumption
3,000 m
3
/h
Equipment
DC connection / AC connection
Ring terminal lug / ring terminal lug
Display
HMI touch display
Communication protocols
Ethernet (optical fiber optional), Modbus
Communication with Sunny String-Monitor
RS485
Color enclosure / door / base / roof, optional silencing
baffle
RAL 9016 / 9016 / 7004 / 7004 / 7035
Configurable grid management functions
Power reduction, reactive power setpoint,
dynamic grid support (e.g. LVRT)
Protective Devices