10  DC Connection

SMA Solar Technology AG

44

SCCP-JP-IA-A4-en-12

Installation Manual

10 DC Connection

Depending on the order option, the DC connection procedure may differ. You must select the relevant section.

10.1 Safety during DC Connection

'$1*(5

Danger to life from electric shock due to live voltage
High voltages are present in the live components of the Sunny Central. Touching live components results in death or

serious injury due to electric shock.

• When working in a high contact-risk environment, wear personal protective equipment.
• Do not touch any live components.
• Follow the instructions precisely.
• Observe all warning messages on the product and in the documentation.
• Observe all safety precautions of the module manufacturer.
• Provided live voltage is not absolutely necessary, always disconnect the following components from voltage

sources before performing any work on the inverter:

– Grid voltage for grid feed-in
– Internal power supply
– DC voltage from the PV array
– Additional external voltages, e.g. control signals from a control room

• Ensure that no disconnected components can be reconnected.
• Wait 15 minutes after switching off the inverter before opening it. This will ensure that the capacitors are

discharged.

• Before working on the Sunny Central, check that all devices are completely voltage-free.
• Ground and short-circuit.
• Cover or isolate any adjacent live components.

Danger to life from electric shock due to live DC cables
DC cables connected to PV modules that are exposed to sunlight carry live voltage. Touching live components results

in death or serious injury.

• Prior to connecting the DC cables, ensure that the DC cables are voltage-free.
• Wear suitable personal protective equipment for all work on the Sunny Central.

Danger to life from electric shock due to ground fault
If a ground fault has occurred, parts of the PV system that are supposedly grounded may in fact be live. Touching system

components that have not been properly grounded results in death or serious injuries from electric shock.

• Before working on the PV system, ensure that no ground fault is present.
• Wear suitable personal protective equipment for all work on the device.

Danger to life from electric shock when entering the PV field
The insulation monitoring with GFDI, Remote GFDI or Soft Grounding does not provide protection from injury when

GFDI is activated. PV modules grounded by GFDI discharge voltage to ground. When entering the PV field, lethal

electric shocks may occur.

• The inverter must be installed in a closed operating area.
• Before entering the PV field, switch the PV array to insulated operation.
• Ensure that the insulation resistance of the PV field is greater than 1 k Ω .