beautypg.com

2 checking the sunny central cabling, 3 inserting fuses and disconnection blades – SMA SC 500CP-10-JP Installation Manual User Manual

Page 73

background image

SMA Solar Technology AG

15  Commissioning

Installation Manual

SCCP-JP-IA-A4-en-12

73

15.2 Checking the Sunny Central Cabling

1. Ensure that all connections are executed in accordance with the circuit diagram.
2. Ensure that the AC, DC and grounding terminals are securely connected.
3. Ensure that there is equipotential bonding between the Sunny Central and the mounting location.
4. Ensure that all terminals in the interface cabinet are securely in place.

15.3 Inserting Fuses and Disconnection Blades

Procedure:

1. If you are using an SMB Connection Kit, insert the disconnection

blades. Use an LV/HRC fuse handle.

7.

Connect the external AC voltage of the MV transformer (to be performed by duly

authorized persons trained in electrical safety only)

MV transformer

documentation

8.

Check the AC grid voltage

15.5.2, page 75

9.

Check the internal voltage supply

15.5.3, page 75

10.

Check grid monitoring

15.6, page 76

11.

Check settings for unused options

15.7, page 76

12.

Switch on the voltage supply and the AC circuit breaker

15.8, page 77

13.

Mount the panels

15.9, page 78

14.

Switch on the Sunny Central

15.10, page 78

Replace LV/HRC size-3 fuses with disconnection blades
If you are using the Sunny Central with the SMB Connection Kit, you will need to replace the extracted LV/HRC

size 3 fuses at the respective fuse inputs with disconnection blades.

Procedure

See Section