beautypg.com

5 connecting the transformer monitoring – SMA SC 500CP-10-JP Installation Manual User Manual

Page 63

background image

SMA Solar Technology AG

12  Cable Connection of External Devices and Connections in the Interface Cabinet

Installation Manual

SCCP-JP-IA-A4-en-12

63

4. Press the shield clamping saddle down onto the shield of the

stripped cable until it snaps into place and fasten hand-tight.

5. Attach the cable to the cable support rail using a cable tie. This will ensure that the cable cannot be pulled out

inadvertently.

12.3.5 Connecting the Transformer Monitoring

The Sunny Central is equipped with a terminal for monitoring the MV transformer which switches the Sunny Central off

immediately under fault conditions. To use the transformer monitoring, an external voltage supply of 230 V/50 Hz must

be provided.

Cable requirement:

☐ The cable must be shielded.

Requirement:

☐ The Sunny Central must be disconnected (see Section 14 "Disconnecting the Sunny Central", page 69).

Procedure:

1. Insert the transformer protection cable in the interface cabinet (see Section 12.2 "Leading the Cables into the

Interface Cabinet", page 58).

2. Connect the cable in accordance with the circuit diagram (see Section 12.3.1 "Connecting the Cables to the

Connecting Terminal Plate", page 59).

3. Remove the shield clamping saddle from the busbar.
4. Press the shield clamping saddle down onto the shield of the

stripped cable until it snaps into place and fasten hand-tight.

5. Attach the cable to the cable support rail using a cable tie. This will ensure that the cable cannot be pulled out

inadvertently.