beautypg.com

9 basic settings, Chap. 9, Basic settings – ARAG Bravo 400S Seletron User Manual

Page 20: Setup "basic settings, Basic implement settings

background image

20

9

BASIC SETTINGS

GUIDED SETUP PROCEDURE UPON FIRST SWITCHING ON

1 LANGUAGE SETTING
- In the "Home" screen (Fig. 38) press

F8

to enter the

Settings

menu (Fig. 39).

- Select

General options > Language

and set the language of Bravo 400S.

- Press

ESC

and return to the

Settings

menu. Now select

Implement

to start guided setup procedure as shown in Fig. 40.

1

Fig. 38

Fig. 39

For a correct use of the keys
during setting, refer to par. 7.4
.

2 IMPLEMENT

- Upon first switching on, Bravo 400S starts the guided setup procedure for the

Implement

: go through each step selecting the desired options (example in Fig. 41).

OK

: next step

ESC

: previous step.

- When the message in Fig. 42 appears, the implement setup is complete. Press

OK

.

- Press

ESC

and return to the

Settings

menu. Now select

Tractor

to start guided setup procedure as shown in Fig. 43.

Fig. 40

OK

Next step

ESC

Previous step

Fig. 41

Fig. 42

BASIC IMPLEMENT SETTINGS

• IMPLEMENT TYPE

Sprayer (Seletron)

: system with Seletron valves.

Sprayer (Electrovalves)

: system with electric-activated valves - with gearmotor.

GPS guidance monitor

: Bravo 400S is only used as a driving aid and does not control spraying (it is not connected to the RCU).

• IMPLEMENT CONNECTION TYPE

Rear 3-point hitch

Towing hitch

Front 3-point hitch
• MAIN VALVE

Main control valve installed on the control unit:

None

2 ways

(drain valve)

3 ways

(main valve)

• SPRAYING SPOT TYPE

Seletron type: single, twin or fourfold

• FLOWRATE REFERENCE SENSOR

Device used to calculate flowrate:

Flowmeter

Pressure

: measured pressure is used to calculate application rate.

Both

: within the working limits the computer uses the flowmeter, otherwise it uses the pressure sensor, ONLY if properly configured.

• SWITCH PANEL TYPE

Sequential section switches

: switch box with sequential control

5 Section switches (Direct)

: 5-way switch box

7 Section switches (Direct)

: 7-way switch box

• TERMINAL NOZZLES

None

"Buffer zone" nozzles

: it selects, through the switch panel, the nozzle to use according to the "Buffer zone", see par. 12.2.1 "Buffer Zone" function enabled on

page 65.

• TANK LEVEL SOURCE

Device used to read tank level:

Manual

: no device connected

Filling flowmeter

Tank level sensor

SETUP

"BASIC SETTINGS"

CONTINUES > > >