beautypg.com

Message – text message setting, Msn – multiple subscriber number, Mtype – transfer method for alarm message – Westermo ID-90 User Manual

Page 77

background image

77

6607-2204

maxretries – Max number of retries on sending

alarm messages

With this command you can set the maximum allowed retries on sending an alarm mes-
sage. The highest allowed value for maxretries = 9 (default = 0).

message – Text message setting

With this command you can set the message text that will be sent at an alarm trig.
There is one entry for each alarm input.

messagex

mm

Set entry number x to message text mm.

messagex

-

Clear entry number x.

messagex

Show entry number x.

message

Show all entries.

Maximum number of entries = 4.
Maximum length of message text = 20.

Example: message command (show all entries)

message1:

Alarm on input 1

message2:

Motor 4 over temp

message3:
message4:

msn – Multiple Subscriber Number

Own MSN (Multiple Subscriber Number)

*: no specific MSN, all incoming calls accepted
The msn is automatically stored to non volatile ram.

mtype – Transfer method for alarm message

With this command you can set up the transfer method for an alarm message.
Selectable transfer methods are SMS, and Hotline text
There is one mtype entry for each alarm input.

mtypex

n

Set entry number x to method number n.

mtypex

-

Clear entry number x

mtypex

?

Show all selectable transfer methods

mtypex

Show entry number x

mtype

Show all entries

Maximum number of entries = 4.

0:

SMS text (UCP) according to UCP- (Universal Computer Protocol)
(default)

1:

Hotline text (expects a acknowledged from receiver to
avoid retries)

2:

SMS text (TAP) (Telocator Alpanumeric Protocol)