beautypg.com

Alarm input settings – Westermo ID-90 User Manual

Page 64

background image

Alarm Input settings

With configuration commands you can set up the conditions for the four alarm inputs.
By entering the command at**alarm the settings made to all four inputs will be presented.
There is one entry for each alarm input and parameter except for transno and maxreties
witch has only one entry each that is common to all alarm inputs.
To execute a ID-90-configuration command out of the AT command mode you
have to issue the command at** together with the parameter name e.g. at**mtype2 1.
In configuration mode or at remote access you just have to enter the parameter name.

Maximum number of entries = 4; x = 1..4
The following parameters has to be set to accomplish the alarm setting.

opnumberx

ISDN number to the operator that provides SMS service

messagex

Alarm text message

mtypex

Type of transfer method for the message (SMS, Hotline text).

recnox

Telephone number to the receiver of the text message.

transno

Transmitter (calling party) ISDN number (Used as information to the
receiver of a SMS call)

maxretries

Max number of retries on failed transmission of a message.

trigcndx

Trig condition for the alarm input Break or Make.

opwdx

Password, used by TAP-protocol

Example:

To set the alarm input 1 to be triggered on a Making contact condition and transfer a
SMS text message to a receiver GSM telephone:

opnumber1 00491722278000
message1 Motor 1 Over temp
mtype1 0

(0 = SMS UCP-protocol [default],
1 = Hotline text, 2 = SMS TAP-protocol)

recno1 0172555555
transno 01721234567

(Common for all alarm inputs)

maxretries 4

(0 default, limits 0..9)

trigcnd1 2

(0 = No cond.(default) 1 = Break cond. 2 = Make cond.)

Note:
It is of importance that you check the physical connection to the alarm inputs before
setting parameter trigcnd to avoid unintentional transmission of alarm messages.

64

6607-2204