Alternatively, you can change the Commission Status property to
Uncommissioned from the Setup tab of the device Web page, which
appears when you select devices in step 1.
3. The Segment Controller places the devices in the soft-offline state (the
device has an application loaded and is configured, but it is offline) and
then unconfigures the devices. The offline devices are highlighted red in
the Segment Controller tree and in the Power Line Repeating Analysis
Web page.
4. To recommission an unconfigured device and place it back online, select
one or more devices to recommission, right-click a selected device, select
Manage, and select Commission from the shortcut menu. You then
select the devices again, right-click a selected device, select Manage, and
select Set Online from the shortcut menu.
Alternatively, you can select the Smart Network Management check
boxes for the Commission Status and Application Status properties
from the Setup tab of the device Web page, and click Submit. You can
also change the Commission Status property to Commissioned and
change the Application Status property to Application Running
(Online), and then click Submit.
Note: Changing the domain ID of the Segment Controller causes all the devices
on the network to be recommissioned automatically and reconfigured to the new
domain ID.
Setting Devices Offline
You can set a device on a power line repeating channel to the offline state in
order to stop running its application. You might want to set a device offline to
test the behavior of other devices on the network. An offline device still receives