Echelon Lumewave CRD 3000 Street Light Bridge User Manual
Page 112

102
Controlling a Street Lighting Network
shortcut menu. The Cleanup dialog opens. Click Cleanup to reset
the Segment Controller.
•
To restore your Segment Controller to its factory default settings
using the console application, enter the factorydefaults command,
or enter the factorydefaults keepipaddrs command to reset the
Segment Controller but keep its basic IPv4 and IPv6 IP addresses.
For more information about using the Segment Controller console
application, see Appendix B of the i.LON SmartServer User’s Guide.
3. Copy the /config/network/<Network>/<Channel>/<Segment
Controller App Device> folder to the
/config/network/<Network>/<Channel> folder on the flash disk of the
target Segment Controller.
4. Reboot the target Segment Controller using the Segment Controller Web
pages or the Segment Controller console application:
•
To reboot your Segment Controller using the Segment Controller Web
pages, right-click the local Segment Controller, select Setup, and
select Reboot from the shortcut menu. The Reboot dialog opens.
Click Reboot to start the reboot.
•
To reboot your Segment Controller using the Segment Controller
console application, enter the reboot command. For more
information about using the Segment Controller console application,
see Appendix B of the i.LON SmartServer User’s Guide.
5. You can open the Web interface of the target Segment Controller and
expand the Segment Controller’s App device in the navigation pane on
the left side. Observe that the functional blocks and data points in the
Segment Controller App device match those of the source. You can click
of the Scheduler functional blocks under the Segment Controller App
device and observe that it has the same configuration as the source.
6. Repeat steps 2–5 to copy the Segment Controller App device
configuration to additional target Segment Controllers.