Street Light Bridge Integrator’s Guide
69
3. The Replace LON Device dialog opens.
4. You can acquire the Neuron ID of the replacement device using a service
pin or you can enter it manually:
•
If you are using the service pin method, press the service pin of
the device. The Neuron ID and program ID of the device are both
entered into the Incoming Service Pin Messages box and they
are input into the Neuron ID or LUID and Program ID boxes,
respectively.
•
If you are using the manual entry method, enter the 12-digit hex
string of the device in the Neuron ID or LUID box.
5. Click OK.
6. Click Submit. The Segment Controller downloads the application and
the configuration data of the original device to the replacement device,