CHAPTER 5: MODE OF OPERATION

PR2: 05/09/12 Page

61 of 162

Benchmark 1.5LN Dual-Fuel Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0C

GF-121

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

5.4 REMOTE SETPOINT MODES

The unit’s setpoint can be remotely controlled by an Energy Management System (EMS) or

Building Automation System (BAS). The Remote Setpoint can be driven by a current or

voltage signal within the following ranges:

4-20 mA/1-5 VDC

0-20 mA/0-5 VDC

The factory default setting for the Remote Setpoint mode is 4 - 20 mA/1 - 5 VDC. With this

setting, a 4 to 20 mA/1 to 5 VDC signal, sent by an EMS or BAS, is used to change the

unit's setpoint. The 4 mA/1V signal is equal to a 40°F setpoint while a 20 mA /5V signal is

equal to a 240°F setpoint. When a 0 to 20 mA/0 to 5 VDC signal is used, 0 mA is equal to

a 40°F setpoint.
In addition to the current and voltage signals described above, the Remote Setpoint mode

can also driven by a RS485 Modbus Network signal from an EMS or BAS.
The Remote Setpoint modes of operation can be used to drive single as well as multiple

units.

NOTE

If a voltage, rather than current signal is used to

control the remote setpoint, a DIP switch adjustment

must be made on the CPU Board located in the

Control Panel Assembly. Contact your local AERCO

representative for details.

In order to enable the Remote Setpoint Mode, the following menu setting must be made in

the Configuration Menu:

MENU

OPTION

SETTING

Boiler Mode

Remote Setpoint

Remote

Signal

4-20mA/1-5V,
0-20mA/0-5V, or Network

Refer to paragraph 3.3 for detailed instructions on changing menu options.
If the Network setting is selected for RS485 Modbus operation, a valid Comm Address must

be entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for

additional information.
While it is possible to change the settings of temperature related functions, the unit is

factory preset with settings that work well in most applications. It is suggested that an

AERCO representative be contacted, prior to changing any temperature related function

settings. For descriptions of temperature-related functions and their factory defaults, refer

to Appendices A and E.

Remote Setpoint Field Wiring

5.4.1

The only wiring connections necessary for the Remote Setpoint mode are connection of the

remote signal leads from the source to the unit’s I/O Box. The I/O Box is located on the

front panel of the boiler. For either a 4-20mA/0-5V or a 0-20mA/0-5V setting, the

connections are made at the ANALOG IN terminals in the I/O Box. For a Network setting,

the connections are made at the RS-485 COMM terminals in the I/O Box. The signal must